Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Using a 4XZM, how can I get relays 3 and 4 to activate with outputs 3 and 4 when the control panel only has two NAC Circuits?

0
10 Posted

Using a 4XZM, how can I get relays 3 and 4 to activate with outputs 3 and 4 when the control panel only has two NAC Circuits?

0
10

When using the 4XZMF zone relay module, the relays will activate when the initiating zone activates: Zone 1 trips Relay 1, Zone 2 trips Relay 2, Zone 3 trips Relay 3, and Zone 4 trips Relay 4. Any zone programmed for alarm will activate its associated relay, and the general alarm relay on the 4XZMF. Any trouble condition on the panel will activate the general trouble relay on the module. Note: If Zone 4 has been programmed as a Supervisory zone, it will activate Relay 4 on the module, but not the General Alarm or System Trouble relay.