Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Two or three fans are installed in the CoolTherm®. Can in case of one fan failure the required determined nominal heat load dissipated?

0
Posted

Two or three fans are installed in the CoolTherm®. Can in case of one fan failure the required determined nominal heat load dissipated?

0

The fans are installed redundantly, i.e. one alone or two are sufficient to operate the system at full capacity. Only the internal rack temperature rises insignificantly here (a few degrees).