to be placed in a containment sump meeting the new performance standards?
No, if only the ALLD is replaced, it will not have to be installed in a containment sump. However, if the STP is also replaced, then the ALLD and STP will have to be placed in a containment sump meeting the requirements of the new performance standards including continuous interstitial monitoring using an electronic sump sensor or vacuum, pressure or hydrostatic interstitial monitoring methods.