Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

On the FCPS-24FS 6/8, can I have two circuits activate notification appliances and the two remaining circuits supply a steady 24 volts?

0
Posted

On the FCPS-24FS 6/8, can I have two circuits activate notification appliances and the two remaining circuits supply a steady 24 volts?

0

All four circuits are factory set as Notification Appliance Circuits (NACs). You can also use Split Alarm Mode, the auxiliary power from terminals 9 and 10, and feed them into terminals 7 and 8 observing the proper polarity. This will activate Outputs 3 and 4 continuously.