Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

OMSC, Section 401.5.1, 804.3.4(4) and C503.8(2) appear to have conflicting requirements for the horizontal clearance from an air inlet. Which section prevails?

0
Posted

OMSC, Section 401.5.1, 804.3.4(4) and C503.8(2) appear to have conflicting requirements for the horizontal clearance from an air inlet. Which section prevails?

0

Section 401.5.1 has a general requirement of 10 feet for horizontal clearance and further states: “…except as otherwise specified in this code.” Sections 804.3.4(4) and C503.8(2) have specific requirements that override the general requirements found in Section 401.5.1.