My project design requires a Shaft Wall system that will be installed to a continuous height of 70 feet. Is this possible with the USG Cavity Shaft Wall System?
For heights exceeding the Limiting Height tables found in the System Catalog (SA926) brochure, we recommend installing the 20 gauge x 6″ C-H Stud in combination with a standard 4″ C-Stud of heavier gauge. The two stud sections should be fastened together (back-to-back with fasteners spaced 12″ o.c. and staggered. The design or project structural engineer must review any design. Q My project design requires a Shaft Wall system that will be installed to a continuous height of 70 feet. Is this possible with the USG Cavity Shaft Wall System?