Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is the retaining flange required for installation of Reliable Institutional Sprinklers?

0
Posted

Is the retaining flange required for installation of Reliable Institutional Sprinklers?

0

The retaining flange is not a required item regarding the listing of the sprinklers. It provides an option to the contractor as a method of securing the piping to prevent axial or lateral movement of the sprinkler either away from the ceiling or the wall by an occupant. If it is not used because of installation constraints, some other approved method of securing the pipe must be provided to prevent an occupant from inflicting self-injury.