Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is spray-on fireproofing, joint compound or mortar an adequate fire stop in construction joints?

0
10 Posted

Is spray-on fireproofing, joint compound or mortar an adequate fire stop in construction joints?

0
10

NO! All material used in firestopping joints such as top or head of wall, perimeter/curtain-wall gap, control joints, etc. will have to pass a cyclical test (500-cycles – UL 2079) and then pass the fire and hose stream test in a fully extended situation. This means that cementitious fireproofing, tape/joint compound or firestopping mortar (typically pink, red, or brown) that is commonly used by drywall contractors at the head of sheetrock walls is definitely out. The problem with these type of materials is that with any movement of the assembly, cracks occur which can allow fire, smoke and toxic fumes through. A material that has expansion and compression characteristics is required. • Can I substitute or mix manufactures products in the system? No! Substituting products within a fire stop system compromises the integrity of the system. Systems are tested with a single manufacturers products to a specific design criteria. Substituting or mixing other manufacturers products will not ful

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123