Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is it possible to change between auto/manual control through Modbus communication ?

0
Posted

Is it possible to change between auto/manual control through Modbus communication ?

0

To change the controller from auto to manual control (Auto off) using the Modbus communications protocol, the Auto/Manual Control bit needs to be changed. This is done by sending a Modbus message of : [01][05][0002][FF00][CRC] A breakdown of this message is as below: [01] Address of controll …