Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is it necessary to use a Network Isolation Choke with the FT 3120 and FT 3150 Free Topology Smart Transceivers?

0
Posted

Is it necessary to use a Network Isolation Choke with the FT 3120 and FT 3150 Free Topology Smart Transceivers?

0

The FT 3120 and FT 3150 Free Topology Smart Transceivers can communicate reliably in the presence of over 3Vrms common mode noise (EN61000-4-6 Level 2) with no changes to your existing PCB. This level of immunity will eliminate the need for a network isolation choke in most light industrial applications. By implementing the modifications to the standard FTT-10A ESD/Surge protection circuitry described above, the FT 3120 and FT 3150 Free Topology Smart Transceivers will be able to communicate reliably in the presence of 10Vrms of common mode noise (EN61000-4-6 Level 3) without the need for a network isolation choke.