Is it a requirement to have a sign posted on the entry door of the location protected by FM-200®?
DuPont™ FM-200® systems in the United States are typically installed in accordance with NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems. Section 4.3.5.5 of the NFPA 2001 (2204 edition) states: 4.3.5.5 Warning and instruction signs at entrances to and inside protected areas shall be provided. The “shall” designation in the NFPA code is a requirement, not an option.