Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is installation of the retaining flange (Viking part number 10599) a UL Listing requirement for Viking Institutional Sprinklers?

0
Posted

Is installation of the retaining flange (Viking part number 10599) a UL Listing requirement for Viking Institutional Sprinklers?

0

No, installation of the retaining flange is not a UL Listing requirement. However, the installing contractor is responsible for ensuring tamper resistance of the final installation. For maximum tamper resistance, it is absolutely necessary to secure the nipple on which the sprinkler is installed to prevent the sprinkler and escutcheon assembly from being pulled away from the ceiling or wall in which it is installed.