Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is fire suppression required for the fuel island at a new gasoline station?

0
Posted

Is fire suppression required for the fuel island at a new gasoline station?

0

A. Yes. FC Section 2206.8 requires the fire protection equipment as follows: An automatic fire-extinguishing system using an extinguishing agent suitable for petroleum fires and installed in accordance with section 904.6 shall be provided for all new flammable liquid fuel dispensing systems subject to section 2206. Fire protection systems at unattended self-service stations shall be monitored by an approved supervising station in accordance with section 901.9.4. It should be noted that this is not applicable to diesel fuel which is a combustible liquid, not a flammable liquid.