Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is emergency power required for a wastewater treatment plant and collection system lift stations?

0
Posted

Is emergency power required for a wastewater treatment plant and collection system lift stations?

0

• Yes in most cases. Maricopa County Environmental Health Code (MCEHC) Chapter I, Section 2, Regulation 5 states: “For systems that treat, or which are designed to treat greater than 10,000 gallons/day, a standby power source shall be provided at all sewage treatment systems and/or pump stations where a temporary power failure may allow a discharge of raw or partially treated sewage. Standby power may be via a standby generator, separate feeders from separate substations, a loop feeder on separate transformers from a common substation, or a high-level alarm with portable generators.