Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

In what way does the output power drive controller of 3-phase-power supply change, if power supply is 2 poles (1 pole)?

0
Posted

In what way does the output power drive controller of 3-phase-power supply change, if power supply is 2 poles (1 pole)?

0

The connectable motor power (motor current) is reduced to ca. 55 % of the drive controller’s rated power You always have to use the assigned mains choke (1 phase mains choke is sufficient). The mains current is ca. 110 % of the original output rated current The 2 phase power supply is not authorized in case of increased rated power (max = 120 % IN).