In the DL06, when Aliases are turned ON, why does the RX/WX instruction show V1200 as CTA200, but the LD instruction doesn ?
This has to do with the fundamental function of the addressing parameter of RX/WX instruction versus the LD instruction. The RX/WX parameter is the remote PLC’s address, whereas the parameter of the LD instruction is the local PLC’s address. Thus, with Aliases turned ON we chose to use the Aliases of the “biggest” DL-PLC that Automation Direct sells (DL450) for the naming of the RX/WX parameter.