Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

If I require Nema 7 rated electrical components, do I specify Nema 4 or 4X for Ingress protection?

0
Posted

If I require Nema 7 rated electrical components, do I specify Nema 4 or 4X for Ingress protection?

0

Nema 7 is typically specified for indoor service for hazardous locations classified as Class 1, Groups A, B, C or D, as defined in by the NEC. Nema 4 or 4X are enclosures specification for outdoor service and non-hazardous locations. If the application is outdoors (non-hazardous), then you must specify either Nema 4 or 4X.