Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How the induction motor startup current multiplication factor is calculated?

0
Posted

How the induction motor startup current multiplication factor is calculated?

0

Solution: The startup current multiplication factor in load-flow is calculated from the inverse of the motor Subtransient Reactance and the Starting Power Factor. The reactance of this impedance (Xd”) can be found in the Component Editor under the ANSI/IEC Contribution subview but the Starting Power (StartingPF) Factor needs to be read from the Induction Motor Subview. The applicable equation is: This Locked Rotor Current Multiplication Factor is multiplied by the Full Load Nominal Current of the motor. The Full Load Nominal Current is calculated from the motor rated values defined in the Induction motor subview window. where: RatedSize is the Rated Size of motor in HP RatedVoltage is the Rated Voltage of the motor in Volts PF is the Power Factor of the motor in p.u. Eff is the Efficiency of the motor in p.u. If you have additional questions, please feel free to contact SKM Systems Analysis, Inc. at the number listed below.