Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How much cross leakage is expected through the energy recovery wheel?

0
Posted

How much cross leakage is expected through the energy recovery wheel?

0

Cross leakage through the energy recovery wheels ranges from 2% to 5% between the supply and exhaust air streams. This amount of cross leakage is minimal and in comfort ventilation applications is perfectly acceptable. These leakage rates are also acceptable for Class 3 Air (toilet room exhaust). According to ASHRAE Standard 62-89R committee, up to 10% cross leakage of Class 3 Air is acceptable for the purposes of energy recovery.