Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How much clearance space is required for WDC Products?

clearance products wdc
0
Posted

How much clearance space is required for WDC Products?

0

The WDC UPS or Power Regulator requires no side or rear operating or service clearance; only front service entry is required. The WDC product sizes are listed in the site planning guide. 7. What is the maximum operating room temperature? The maximum operating room temperature for the Power Regulator and UPS control cabinet is 100 degrees F. The battery cabinet should be operated in a conditioned environment at an ideal temperature of 72 to 77 degrees F(23º to 26º C) and a maximum temperature of approximately 85 degrees F (30º C). Temperatures over 85 degrees will shorten the battery life. 8. What is the life of the UPS batteries? The UPS battery life can vary greatly depending on operating temperature, number of discharges and type of discharge. Typical battery longevity is 4 to 7 years. WDC offers battery replacement services. 9. How many minutes of battery back up will I get? The amount of battery back up time depends on the amount of power being drawn by the load. Most continuous he

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123