How much clearance around my Data Aire unit is required for servicing?
Data Aire recommends 36″ on the front and two sides of floor mounted units, and on all sides for both ceiling and outdoor units. What are the typical pressures for discharge and suction? Discharge pressures range between 215 to 250 PSI. Suction pressures range from 60 to 70 PSI. What are the typical temperatures for superheat and sub-cooling? Sub-cooling temperatures range between 10 to 12 degrees F. Superheat temperatures range between 10 to 14 degrees F. with unit return air at 68 to 74 degrees. Are traps required in refrigerant piping run with air cooled units? Yes, trapping is required on both the discharge and/or suction lines. Discharge lines, also called hot gas lines, should be trapped at the top (inverted) and bottom, as well as every 15-20 feet of vertical rise as applicable. Suction lines should be trapped in a similar fashion. How much steam is generated by the Nordec humidifier? Can it be adjusted? The amount of steam generated depends on the model of humidifier you have i