Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How many fasteners are needed to achieve FMRC I-60 and I-90 psf wind uplift resistance when 1/4″ DensDeck is used as an overlay board?

0
Posted

How many fasteners are needed to achieve FMRC I-60 and I-90 psf wind uplift resistance when 1/4″ DensDeck is used as an overlay board?

0

The number of fasteners required to achieve I-60 and I-90 psf wind uplift resistance for 1/4″ DensDeck overlayment depends on the type of membrane used. For mechanically attached roof coverings, only four fasteners per 4′ x 8′ sheet of 1/4″ DensDeck are necessary. These fasteners keep DensDeck in place while the membrane is being attached. The number of fasteners needed to attach such membranes far exceeds the number of fasteners required to achieve 90 psf wind uplift rating.