Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How many computers can I connect to a 30mA RCD protected circuit?

0
Posted

How many computers can I connect to a 30mA RCD protected circuit?

0

The switch mode power supply in a computer will leak up to 3.5mA to earth. A Hager 30mA RCD will not trip at 15mA but will trip at a point above 15mA and below 30mA. We would suggest no more than 4 computers on the one RCD circuit in order to ensure that unwanted tripping of the RCD does not occur.