Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How low can a raised floor height be constructed and still use UFAD?

0
Posted

How low can a raised floor height be constructed and still use UFAD?

0

A. We believe that UFAD systems can go as low as 6″ FFH (4-5/8″ of clear space) to 8″ FFH provided our column units are spaced in frequent points on the floor plate to ensure good air distribution. This low FFH is very applicable for general office where electrical plug and play conduit is only 7/8″ diameter and voice and data cables are not intensive. The floor height needs to be greater for applications where cable trays are being used.