Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How does ASHRAE 90.1 2001 impact HVAC systems?

ASHRAE HVAC impact SYSTEMS
0
Posted

How does ASHRAE 90.1 2001 impact HVAC systems?

0

Text excerpts from the above ASHRAE Energy Standards for Buildings, except Low Rise Residential Buildings (See enclosed scans of relevant pages): Purpose of Standard: • To provide minimum requirements for energy-efficient design of buildings 6.2.5.3 System Balancing • All HVAC systems shall be balanced • Written balancing report provided to owner for conditioned areas exceeding 5,000ft^2 (500m^2) • Hydronic Systems shall be Proportionately Balanced in a manner to first minimize throttling losses, then the pump impeller shall be trimmed or [max] speed adjusted to meet design flow conditions Exceptions: • Need not trim impeller or adjust speed if: • Pumps equipped with motors 10 hp (7.5 kW) or less • When throttling results are not > 5% of nameplate power draw, or 3 hp (2.2 kW), whichever is greater, above power required with trimmed impeller. 6.3.1 Economizers • Each Cooling system having a fan shall include either an air or water economizer 6.3.4 Hydronic System Design and Control • HV