Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How do I wire my oil-fired boiler to a CK-61 control kit and power venter?

0
Posted

How do I wire my oil-fired boiler to a CK-61 control kit and power venter?

0

* Method #1: Remove the wire from B1 terminal on boiler and re-route to one side of the WMO-1. Then from the other side of the WMO-1 run up to T3 in the CK-61. Run a new wire from terminal B1 on boiler to T1 on CK-61. Finally run a wire from T2 in the CK-61 to B2. * Method #2: Inside primary control, unscrew the wire nut that connects the orange wire to the two blacks which feed the ignition and burner motor. Separate the orange from the two blacks and route the orange wire to T1 on CK-61. Run new wire from T3 to one side of the WMO-1. The other side of WMO-1 to same two black wires, which feed the ignition and burner motor. Run T2 to neutral whites in the primary control * For terminals L1, N, & M follow instructions in the CK-61 manual.