Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How do I tell what the temp of the water, supply and return, was at the time of a fault on an W/M Ultra boiler?

fault Return supply time Ultra water
0
Posted

How do I tell what the temp of the water, supply and return, was at the time of a fault on an W/M Ultra boiler?

0

You can unlock the panel and go to error and proceed with hitting the step button to obtain: 1) error code; 2) state of operation when the error occurred e.g stdby , ignition , etc.; 3) supply water temp at time of error; 4) return water temp at time of error; 5) whether the boiler was in a dhw call for heat or a boiler call for heat; and 6) outdoor temp at the time of error if the sensor is hooked up.