How do I set up the a 4-20 mA output from a 3B Series module to map with either the – 10 V to +10 V or 0 to + 10 V output signal?
A. All modules are shipped to provide a 4-20 mA current output corresponding to a 0 to + 10 V voltage output. This current output range can be quickly changed to correspond to a – 10 V to + 10 V output by selection of a supplied jumper on the bottom of the module. A jumper also exists to change the output current range to 0-20 mA.
Related Questions
- Im using a 3B39 isolated output module. When I apply a 0 to + 10 V input signal to the screw terminals just above the module on the backplane, I can get 4-20 mA output signal?
- I want to measure a 4-20 mA signal with a 6B Series subsystem. Which module is best to use, the 6B11 or 6B12?
- Can I order a custom-ranged 5B module with a 0 to +10 V or -10 V to +10 V output range?