Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How do I select the AVD supply air dampers and thermostats?

0
Posted

How do I select the AVD supply air dampers and thermostats?

0

Take the known CFM for each zone then go to table 1 and select the corresponding size. The AVD damper is usually the same size as the duct. Remember use one thermostat per zone – not per damper. Two dampers can be connected to the same channel for larger zones. 3. How should I size the RAD bypass damper? There are two methods to size the RAD bypass damper. • If there is less than six(6) zones the required capacity is determined by subtracting the capacity of the smallest AVD terminal from the HVAC unit’s design CFM. • If the system has six(6) or more zones an arbitary factor of .75 * unit CFM is used to determine bypass air requirements. • NOTE: Depending on the size of the system more than one(1) RAD bypass damper may be required. Starzone 3000 Accessories SC100- Single unit controller to integrate “non-zoned” HVAC units into the Starzone 3000 system. TOA- Outdoor air sensor to shut off heating at specific outdoor temperatures. Starcom95 (windows) Software and the Starcom HUB The star

Related Questions