Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How do I go about sizing a VFD for a Tower Tech Modular Cooling Tower?

0
Posted

How do I go about sizing a VFD for a Tower Tech Modular Cooling Tower?

0

The VFD’s size must be based on full load amps (FLA) including the motor service factor. For example, a Tower Tech TTXL-081975 tower module has eight 7.5 horsepower motors, each with a FLA of 12 amps at 480 volts. Adding the 1.15 service factor results in 110.4 full load amps, therefore the VFD should be sized to support 110.4 FLA.