How do I Download/Upload with 1706S Instrument Configuration Software on faster computers?
Try lowering the baud rate for the communication. Do this in the 1706S Software setup and on the minilink using the jumpers. Where are the electrical connections for 120 to 350Vdc on the 2002N Modcell instrument? The 120 – 350 VDC power is connected at the AC connection terminals on the 2002N instrument. Connect the Positive to L1 and Negative to N/L2. How do I connect to attributes that are not connectable Examples of atributes that are not connectable are: Alarm setpoints in PA, PAD blocks, SPMS, OPMS in PID block. If you can not see an attribute in the connection list (Incoming Inputs) of the block, then you can not connect to it by regular connection. But you can use the SM block (Supervisory Mesage). The SM block can be used to set or write values to an attribute. This setting/writing has to be initiated by a low to high transition of a discrete signal and is a one time transaction. For updates (writing or setting of the value at specified intervals), you need to initiate the tran