Fan coil units are defined as including central ventilation to the space, which Specific Fan Power (SFP) and flow rate should I enter for this system?
The auxiliary energy figures for this system include an allowance for the fans in the fan coil units, (and there is a minimum acceptable performance figure in the HVAC guide – 0.8 based on the average of all fan coils). The SFP that users input should be just for the central plant – the fan coil allowance will be includedautomatically. Similarly, the flow rate should be for the central plant.