Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Does the installation of an RCCB affect fault loop impedance?

0
Posted

Does the installation of an RCCB affect fault loop impedance?

0

Yes. The Wiring Rules require a protective device to operate in not more than 400ms under earth fault conditions. An RCCB always operates in less than 300ms and so meets the earth fault requirements. When conducting an earth fault loop impedance test, an internal connection is made by the test instrument which causes an RCCB to trip. Therefore the fault loop test is satisfactory (see Cl 6.3.4.2 of the wiring rules).