Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Does the DDX deluge valve require a check valve for preaction system applications?

0
Posted

Does the DDX deluge valve require a check valve for preaction system applications?

0

No, the DDX utilizes an intermediate chamber in its seat design, which separates the inside of the valve body with the alarm outlet piping which is open to atmosphere. Therefore, supervisory air pressure can fill the valve body and the system piping without separation by a riser check valve.