Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Does the AAV work on Closed and Open systems?

AAV closed SYSTEMS
0
Posted

Does the AAV work on Closed and Open systems?

0

Yes, on newly installed closed systems there will be a small pressure drop (around 15%) as the air is vented from the fresh water, but any further pressure drop will be due to loss of system water (leaks). Some installers are priming a newly installed system to about 10% more than it’s operating pressure to compensate on a system fitted with AAV’s. ” On a Closed system will fitting automatic vents cause the pressure to drop to zero and the boiler stop operating?” The answer is linked to the above – continual venting will be due to new air entering the system (through microgaps in joints etc), once the fresh water has vented its 15% of air the volume of water cannot further reduce in size – so if you still experience pressure drop it’s due to water loss.