Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Does Siemens have breaker lugs rated for use with 90 Deg C wire?

breaker deg LUGs rated Siemens wire
1
Posted

Does Siemens have breaker lugs rated for use with 90 Deg C wire?

0

The short answer is no – nor does any other breaker manufacturer. However, 90 Deg C insulated wire CAN be used IF it is sized per the 75 Deg ampacity column in the NEC tables. In fact, with most of Siemens 100% rated circuit breakers, 90 Deg. Cable is required, but it must be sized per the 75 Deg ampacity.