Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Does a 2-pole ground fault circuit interrupter (GFCI) circuit breaker provide Personnel Protection in accordance with the NEC when no neutral is used?

0
Posted

Does a 2-pole ground fault circuit interrupter (GFCI) circuit breaker provide Personnel Protection in accordance with the NEC when no neutral is used?

0

Yes. If the load does not require a neutral, for example a 240V only load, the GFCI breaker still provides the required ground fault protection. Regardless of whether or not a LOAD neutral is used, the white wire attached to the breaker MUST be connected to the panel neutral bar.