Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Do the intumescent free approvals require a smoke control gasket at the meeting edges of pairs?

0
10 Posted

Do the intumescent free approvals require a smoke control gasket at the meeting edges of pairs?

0
10

The Pemko S77 meeting edge smoke control gasket is only required if a smoke and draft control opening has been specified. Concealed intumescent is still required on all 45, 60 and 90 minute meeting edges.