Can the WinPLC be used with an operator interface?
Yes, the C-More and C-More Micro panels have Entivity Modbus drivers. C-More panels can use Modbus RTU(serial) and Modbus TCP/IP(Ethernet). C-More -R panels do not have Ethernet. C-More Micro panels can use Modbus RTU(serial) only. The WinPLC must have Modbus RTU enabled, this is set in the I/O view and is off by default. Both require that the Think and Do project be saved to disk so you can reference the .MAP file for the I/O mapping in the device driver configuration. Note! If you make changes to the WinPLC project you must re-read the .map file for the addresses to be corrected in the panel.