Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can the ECOM/ECOM100s red error light be monitored from ladder logic (e.g. SP bits) and will the ECOM/ECOM100 recover automatically?

0
Posted

Can the ECOM/ECOM100s red error light be monitored from ladder logic (e.g. SP bits) and will the ECOM/ECOM100 recover automatically?

0

If the error (ERR) light comes on (or is flashing), this means a fatal error occurred and for this reason it cannot be monitored from ladder logic (i.e. the firmware has stopped running; the ECOM/ECOM100 is dead; it is not doing anything). Before it died the SP bit may or may not have been set or cleared; it is completely unpredictable. After the error light comes on, you will have to power cycle the ECOM/ECOM100 to get it up and running again; the error cannot be reset automatically when the cause is removed.