Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can the BlueLynx BLM-TX/BLM-RX units be configured to sense voltage?

0
Posted

Can the BlueLynx BLM-TX/BLM-RX units be configured to sense voltage?

0

The BLM-TM transmitter module can be configured to sense 1-5 volts or 4 to 20 mA. They are usually shipped configured to 4-20 mA. Some units built prior to January 2003 were shipped as 1-5 VDC. To change from one configuration to the other, it is necessary to install or remove a jumper kit. If the jumper kit is installed, the unit will sense 4-20 mA. If it is removed, the unit will sense 1-5 VDC. If you are uncertain which configuration you have, measure the resistance between the loop plus and minus terminals. A reading of 250 ohms indicates the jumpers were installed, and the unit is configured to sense 4-20mA signals. All units are shipped with a parts bag containing extra jumpers and precision 250-ohm resistors. Placing a jumper from the kit bag across the plus and minus terminals will configure the unit to sense 4/20 mA signals. To install or remove the jumpers, you must refer to the manual that came with the units. The BLM receiver always puts out a current, not a voltage. If you