Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can the 2200 series do an analog retransmission of PV or SP?

analog PV retransmission SERIES SP
0
Posted

Can the 2200 series do an analog retransmission of PV or SP?

0

Yes. With an analog dc board (D3) installed in slot 1A only, the unit can retransmit Process Variable, Setpoint, Error, and Control % Output. The retransmission signal is available as 0-20mA, 4-20mA, 0-5V, 1-5V, or 0-10V. Note: To retransmit a signal as a voltage, the output must have a resistor in parallel with 1A and 1B, 250 ohm for 5 volt, 500 ohm for 10 volt.