Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can Siemens circuit breakers be used in 400Hz applications?

0
10 Posted

Can Siemens circuit breakers be used in 400Hz applications?

0
10

All Siemens circuit breaker with thermal-magnetic trip units may be applied on 400Hz systems, up to 480V, following the de-rating table in the Siemens 2004 SPEEDFAXTM on page 6-100. The interrupting rating will be 5kA or 10% of the 60Hz rating, whichever is greater. Siemens circuit breakers with electronic trip units have not been tested for 400Hz applications.