Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can Midel transformers be installed without fluid containment?

0
Posted

Can Midel transformers be installed without fluid containment?

1

This depends greatly on the local government in the area that you are installing the transformer. The German Federal Department of the Environment, UBA (Umweltbundesamt) has identified Midel as being non-water hazardous, which brings reduced requirements for containment. FM GlobalĀ® (Factory Mutual) has also increased the volume of fluid before containment is required from 1,940 litres to 10,000 litres where an approved biodegradable fluid such as Midel is used instead of mineral oil.