Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can I use a generator whose wattage exceeds the wattage on the Reliance Pro/Tran® transfer switch?

0
Posted

Can I use a generator whose wattage exceeds the wattage on the Reliance Pro/Tran® transfer switch?

0

This is acceptable for peak wattage but not recommended for running wattage. Pulling more than the rated wattage through the Reliance Pro/Tran® transfer switch could burn out the neutral wire, overheat the main wiring in the transfer switch and cause a fire. To insure proper safety precautions, a suitable double pole breaker should be installed between the generator and the transfer switch when the running wattage of the generator exceeds the rating of the transfer switch. See the Power Inlet Box with Built-in Circuit Protection in the T/Power accessories section.