Can I set-up the APs output 1 to trigger between 4 and 8 PSI , and output 2 to turn on when I have a stable reading within this window?
Yes, by using Window mode (F-4) on your AP sensor. What you would do is set-up the H to be 8 and the L to be 4. When you are inside of the H and L values, Output 1 will turn on, and if you are within the stability levels calculated automatically inside the AP sensor; Stability High (SH) = H – (H-L)/4 = 7 PSI, and Stability Low (SL) = L + (H-L)/4 = 5 PSI, output 2 will turn on.