Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can I interrupt the perimeter intumescent/smoke seals with hardware?

0
Posted

Can I interrupt the perimeter intumescent/smoke seals with hardware?

0

If there is a smoke requirement for the door and the smoke seal is interrupted by the hinge locations, it will be necessary to run another length of the seal alongside the hinge blade to maintain continuity. The intumescent seal position has to remain as tested and should not be re-routed to another position; doing so may negate the performance of the door. In placing the intumescent seal in a different location to that tested, the seal may not react as it did during testing. One possible consequence of this could be ineffectual sealing and clamping of the door leading to premature failure.