Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can fire test data obtained from curcular hollow steel (CHS) sections be used for the fire protection of solid steel bars or rods?

0
Posted

Can fire test data obtained from curcular hollow steel (CHS) sections be used for the fire protection of solid steel bars or rods?

0

Fire protected solid steel bars may behave differently from fire protected hollow steel sections in fire. The use of a specific protection system and its thickness should be based on a proven capabiity suitable to the application. It is necessary to generate a multi-temperature thermal analysis based on the fire testing of solid bars over a range of diameters. Consult the fire protection manufacturer for advice on the use of specific products. NOTE – ASFP Technical Committee agreed on 080513 to develop a specific ASFP fire test protocol for assessing the fire protection for solid steel bars and rods.

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.

Experts123