Can a Protectowire Linear Heat Detection system provide Pre-Alarm capability?
Yes, by utilizing Tri-Wire (PHSC-6893-TRI) a Pre-Alarm indication is provided at 155F (68C) and an Alarm indication is provided at 200F (93C). Like all Protectowire Linear Heat Detectors, TRI-Wire is compatible with the unique Protectowire Alarm Point Location Meter. Depending upon the model control panel the meter will display the location of the Pre-Alarm point or the Alarm point of the Tri-Wire Linear Heat Detector.
Related Questions
- What is the maximum length of Protectowire Linear Heat Detector that can be placed on a single detection zone of a Protectowire FireSystems Control Panel?
- How is the location of overheat or fire determined in a Protectowire Linear Heat Detection zone?
- Can a Protectowire Linear Heat Detection system provide Pre-Alarm capability?