Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Are there differences in transmission losses between overhead lines and power cables?

0
Posted

Are there differences in transmission losses between overhead lines and power cables?

0

In principle, the equivalent conductor size of underground cables is much larger than that of the OHL (i.e. a copper cable of 2500 mm2 corresponds with an aluminium overhead conductor of 1500 mm2). Consequently, the electricity joule losses are lower. At high circuit loads, OHL losses can be up to three times the cable losses due to the smaller conductor size of OHL. Conversely, UGC losses would be slightly higher for low load currents. The actual load current on any transmission circuit will vary with both time of day (higher loads during the day, less at night) and season (higher in winter than summer), so calculation of the difference in losses would require data from the transmission company on forecast load and peak demands.